ZN yn11接地变压器变比误差测量 | |
江门市电力工程输变电公司 李大厚 卢玉成 | |
为节省流量,手机版未显示文章中的图片,请点击此处浏览网页版 | |
摘 要:针对广东省广电集团有限公司江门供电分公司220 kV群星变电站站用变压器变比误差测量值与厂家提供数据相差太大的情况,提出了一种测量带二次绕组接地变压器变比误差的方法。介绍了该方法的原理和测量步骤,并以SC9-630/11.250/0.4型变压器为例分析了测量结果的正确性。
关鍵词:接地变压器;ZN,yn11联结方式;变比;误差
Measurement of noload voltage ratio error of ZN,yn11 grounding transformers
LI ahou1,LU Yucheng2
(1.Jiangmen Power Transmission and Substation Engineering Co., Jiangmen,Guangdong 529030,China;
2.Henan Installation Group Co.,Ltd.,Luoyang,Henan 471000,China)
Abstract:In view of the considerable difference between the measured noload voltage ratio error of the transformer in 220 kV Qunxing Substation of Jiangmen Power Supply Branch,GPG and the specification of the manufacturer,this paper presents a method to measure the ratio error of the grounding transformer with secondary windings.The principles and the procedures of the proposed method are described,and the accuracy of the results validated with a SC9-630/11.250/0.4 transformer.
Keywords:grounding transformer;ZN,yn11 connection;no-load voltage ratio;error
3~10 kV电力输配电系统一般都为不直接接地系统,为了保障系统单相接地时仍能继续运行,往往在变电站内利用ZN,yn11接地变压器的人工接地点,并加装消弧装置来限制单相接地故障电流,确保电网安全。对于这类变压器的变比测量,运用现有各个厂家生产的变比电桥难以得到正确的测量结果。为此有很多用户只能釆用电压表比较法进行测量,但由于受电压波动、测量仪表误差及人为误差等因素的影响,往往也难以得到理想的结果。
1 变比误差测量中发现的问题
广东省广电集团有限公司江门供电分公司220 kV群星变电站站用变压器为许继电气股份有限公司产品,型号为SC9-630/11.250/0.4,联结组别为ZN,yn11,电压组合为(11±2×2.5%)/0.4 kV,额定容量为630 kVA;使用的变比测量仪器为金源科技有限公司生产的JYT变比测量仪。按照试验的步骤输入变比、联结组别及分接头值进行测量,最大变比误差为9.85%,而厂家出厂报告中变比误差均在0.1%以下。
2 ZN,yn11变压器变比误差测量方法
以ZN,yn11变压器U相和V相的变比误差测试为例。如图1所示,短接变压器低压侧V2相和W2相,有如下关系式: (图片) (图片) (图片) (图片) (图片) | |